INSPECTION
PROCEDURE
1. INSPECT CHARCOAL CANISTER ASSEMBLY
| (a) Visually check the charcoal canister assembly for cracks or damage. If cracks or damage is found, replace the charcoal canister assembly. | 
 | 
(b) Check the canister operation.
 
 | *1 | Connector | 
| *a | Vent Line Port | 
| *b | Air Inlet Line Port | 
| *c | Purge Line Port | 
| *d | Air | 
(1) With the purge line port and connector closed, blow air at 5 kPa (0.1 kgf/cm2, 0.7 psi) into the vent line port and check that air flows from the air inlet line port.
| (2) With the vent line port and connector closed, blow air at 5 kPa (0.1 kgf/cm2, 0.7 psi) into the air inlet line port and check that air flows from the purge line port. If the result is not as specified, replace the charcoal canister assembly. | 
 | 
(c) Check for air leaks.
| (1) Connect a pressure gauge to the vent line port of the charcoal canister assembly. | 
 | 
(2) With the purge line port, air inlet line port and connector closed, apply pressurized air at 19.6 kPa (0.2 kgf/cm2, 2.8 psi) into the vent line port, and then confirm that pressure is retained for 1 minute.
If the result is not as specified, replace the charcoal canister assembly.
 Installation
 Installation
	 Egr Cooler
 Egr Cooler
	 Problem Symptoms Table
 Problem Symptoms Table
	 Check Bus 5 Line for Short to +B
 Check Bus 5 Line for Short to +B